EasyManua.ls Logo

Omron 3G3M1-A4004-ECT - Page 575

Omron 3G3M1-A4004-ECT
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Bit Name Description
0 Ready to switch on These bits give the status.
For details, refer to State Coding on page
A-5.
1 Switched on
2 Operation enabled
3 Fault
4
Voltage enabled
*1
5 Quick stop
6 Switch on disabled
7 Warning This bit indicates that warning (9-1-3 Minor Fault Code List
on page
9-25) is occurring. The inverter operation continues.
8
Reserved Not used. Always keep them at 0.
9 Remote This bit indicates that the inverter is currently controlled with
Controlword.
After initialization is completed, this bit changes to 1 (remote).
When 0 (local) is given, it indicates that the support software
has the control right to the inverter.
10 to 15
Reserved Not used. Always keep them at 0.
*1. The Voltage enabled bit indicates that the main circuit power supply voltage is applied when it is 1.
Index
(hex)
Sub-
index
(hex)
Object name
Setting
range
Unit
Default set-
ting
Data
attrib-
ute
Size
Ac-
cess
PDO
map
Complete
access
Modes of
operation
6042 --- vl target velocity -32,767 to
32,768
r/min 0 --- 2 bytes
(INT16)
W Possi-
ble
--- vl
This object commands the velocity and rotation direction to the inverter.
When set to a negative value, the inverter operates in the reverse direction.
Index
(hex)
Sub-
index
(hex)
Object name
Setting
range
Unit
Default
setting
Data
attrib-
ute
Size
Ac-
cess
PDO map
Complete
access
Modes of
operation
6043 --- vl velocity de-
mand
--- r/min 0 --- 2 bytes
(INT16)
RO Possible
(TxPDO)
--- vl
This object gives the operation velocity of the inverter in increments of 1 r/min.
Index
(hex)
Sub-
index
(hex)
Object name
Setting
range
Unit
Default
setting
Data
attrib-
ute
Size
Ac-
cess
PDO map
Complete
access
Modes of
operation
6044 --- vl velocity actual
value
--- r/min --- --- 2 bytes
(INT16)
RO Possible
(TxPDO)
--- vl
This object gives the output velocity of the inverter in increments of 1 r/min based on 1st Motor
Pole Number (P01) (3007-02 hex).
Display contents depend on the control mode of the inverter.
IM V
ector control with speed sensor, IM V/f control with speed sensor: Actual velocity
Vector control without speed sensor: Estimated velocity
V/f control: Output velocity (before slip compensation)
Appendices
A-29
M1 Series EtherCAT Type User’s Manual (I670)
A-2 CoE Objects