Index
(hex)
Sub-
index
(hex)
Pa-
rame-
ter No.
Function name Monitor or data range
Default
data
Set-
ting
dur-
ing
RUN
Unit
PDO
map
1C E127 1st 2-step Accel-
eration Switching
Frequency
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.00 to 590.00
0.00 --- Hz Possible
1D E128 2nd 2-step Accel-
eration Switching
Frequency
1E E129 1st 2-step Decel-
eration Switching
Frequency
1F E130 2nd 2-step De-
celeration Fre-
quency
20 E131 Frequency Cal-
culation Opera-
tion T
arget 1
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
1: Analog voltage input (terminal
[AI1])
5: Pulse train input
7: EtherCAT
1
--- --- Possible
21 E132 Frequency Cal-
culation Opera-
tion Target 2
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
1: Analog voltage input (terminal
[AI1])
5: Pulse train input
7: EtherCAT
7
--- --- Possible
22 E133 Frequency Cal-
culation Operator
Selection
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Addition (E131 + E132)
1: Subtraction (E131 - E132)
2: Multiplication (E131 x E132)
0 --- --- Possible
23 E134 Frequency Addi-
tion Amount
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.00 to 590.00
0.00 --- Hz Possible
24 E135 Frequency Addi-
tion Sign Selec-
tion
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Frequency command + E134
1: Frequency command - E134
0 --- --- Possible
28 E139 Overvoltage/
Overcurrent Re-
start Function
Selection
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Immediately trip
4: Restart at the frequency selected
by E152
0 --- --- Possible
Appendices
A-121
M1 Series EtherCAT Type User’s Manual (I670)
A-4 Lists of Manufacturer Specific Objects 2
(Inverter Parameters)
A
A-4-6 E Group Parameter List (Terminal Functions)