Power
supply
line
Stand-
ard ap-
plicable
motor
(kW)
Inverter model
Specifi-
cations
Molded case cir-
cuit breaker
(MCCB)
*1
Earth leakage circuit breaker (RCD/
ELCB)
*1
Rated current Rated current Sensi-
tivity
cur-
rent
*2
Max.
fault
loop im-
pedance
With DC
reactor
Without
DC re-
actor
With DC
reactor
Without
DC re-
actor
Single-
phase
200 V
0.1 3G3M1-AB001-ECT HHD 5 5 5 5 30 mA 200 Ω
0.2 HND
3G3M1-AB002-ECT HHD
0.4 HND 10 10
3G3M1-AB004-ECT HHD
0.55 HND 10 10
0.75 3G3M1-AB007-ECT HHD 15 15
1.1 HND 15 20 15 20
1.5 3G3M1-AB015-ECT HHD
2.2 HND 30 30 30 30
3G3M1-AB022-ECT HHD
3 HND 40 40
3.7 3G3M1-AB037-ECT HHD 40 60 40 60
*1. The frame size and model of MCCB, RCD or ELCB (with overcurrent protection function) change according to the ca-
pacity of the power transformer. For details on selection method, refer to related technical data.
*2.
The sensitivity current setting of the TT system differs according to each country. Follow the instructions of the relevant
authority.
• Use the inverter in an environment that does not exceed pollution degree 2. In pollution
degree 3 or 4 environments, install the inverter in a panel that satisfies IP rating IP54 or
higher.
• T
o prevent operators from electric shock caused by live parts, install the inverter, AC re-
actor (ACR) or DC reactor (DCR), and input filter or output filter inside a panel with IP2X or
higher. When an operator can easily touch the panel, ensure that the protection grade of
the top surface of the panel is IP4X or higher.
• Do not directly connect copper wire to the ground terminal. Use tin-plated or equivalent-
plated crimped terminals for connections.
• When the inverter is used at locations 2,000 m or higher above sea level, the insulation of
the control circuit is the basic insulation. The inverter cannot be used at locations 3,000 m
above sea level.
• Use wires stipulated in IEC60364-5-52.