Power supply line
Standard applicable motor (kW)
Inverter model
Specifications
Molded
case circuit
breaker
(MCCB) or
earth leak-
age circuit
breaker
(RCD/
ELCB) rat-
ed current
*1
Recommended wire size (mm
2
)
For main circuit
For control circuit terminal
Control power supply auxiliary input R0, T0
Main power
supply in-
put [L1/R,
L2/S, L3/
T]
*2
Inverter
ground
[
]
*2*3
Inverter output [U, V, W]
*2
For DC reactor connection [P1, P(+)]
For braking resistor connection [P(+), DB]
*2
With DC reactor
Without DC reactor
With DC reactor
Without DC reactor
With DC reactor
Without DC reactor
Three-
phase
200 V
0.1 3G3M1-
A2001-ECT
HHD 5 5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 0.75 -
0.2 HND
3G3M1-
A2002-ECT
HHD
0.4 HND
3G3M1-
A2004-ECT
HHD
0.75 HND 10
3G3M1-
A2007-ECT
HHD
1.1 HND 10
1.5 3G3M1-
A2015-ECT
HHD 15
2.2 HND 20
3G3M1-
A2022-ECT
HHD
3 HND 20 30
3.7 3G3M1-
A2037-ECT
HHD 4 4
5.5 HND 30 40 6 6 4
3G3M1-
A2055-ECT
HHD 50 4 4 4
7.5 HND 40 75 6 10 6 10 6 10
3G3M1-
A2075-ECT
HHD
11 HND 50 100 10 16 10 16 10 16
3G3M1-
A21
10-ECT
HHD
15 HND
75 125 16 25 16 16 16 25
3G3M1-
A2150-ECT
HHD
18.5 HND 100 150 25 35 25 35
3G3M1-
A2185-ECT
HHD 2.5
22 HND 175 35 50 25 35
*1. The frame size and model of MCCB, RCD or ELCB (with overcurrent protection function) change according to the ca-
pacity of the power transformer
. For details on selection method, refer to related technical data.
*2.
The recommended size of wire to the main circuit terminal is the size when PVC wire having an allowable temperature
of 70°C and a rated voltage of 600 V is used, and the ambient temperature is 40°C.
*3. Only one wire of recommended size can be connected to the ground terminal.
2 Design
2-78