EasyManua.ls Logo

Omron CJ1W- ECT21 - CJ1 W-ECT21 Setting Procedure

Omron CJ1W- ECT21
154 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendices
A - 4
CJ-series EtherCAT Slave Units Operation Manual (W541)
This section provides the setting procedure for establishing EtherCAT Slave Unit communications.
1 With the power OFF, set the unit number and node address with the corresponding hardware
switches. Refer to 2-1-3 Switch Settings on page 2-6.
2 Mount the EtherCAT Slave Unit to the CPU Rack. Refer to 2-2-2 Mounting to a CJ-series PLC
on page 2-8.
3 Connect the communications cable between the EtherCAT master and EtherCAT Slave Unit.
Refer to 2-3 EtherCAT Network Wiring on page 2-10.
4 Connect the CX-Programmer to the CJ-series CPU Unit.
5 Turn ON the power supply to the CJ-series PLC.
6 Place the CX-Programmer online with the CJ-series CPU Unit.
7 Create the I/O table with CX-Programmer. Refer to A-5 Creating I/O Tables on page A-24.
8 Set the I/O Communication Area Setting Table. Refer to 3-4-2 Setting Procedure with the
CX-Programmer on page 3-19.
The example is shown below.
A-1-4 CJ1W-ECT21 Setting Procedure

Table of Contents

Related product manuals