110
The following graph shows the voltage output characteristics of the Analog Out-
put Unit.
Output voltage (V)
10
5
0
5
10
F800 FC00
Output data (hexadecimal)
0000 0400 07FF
Note 1. If the setting pins are set to prohibit negative voltage output, no negative
voltage will be output.
2. In 2s complement, 1 is FFFF, by subtracting 1 continuously, the smallest
value will be F800.
Current Output Data between 0000 to 07FF (hexadecimal) for output from the CPU is converted
into a current of 0 to 20 mA and output.
Bits 11 to 14 of the output data have nothing to do with output current (i.e., 0 mA is
output for 0000 and 7800 (hexadecimal)). Bit 15 must be always set to 0. If bit 15
is set to 1, the data conversion of the Analog Output Unit may take longer.
15
10 9 8 7 6 5 4 3 2 1 0
MSB LSB
These four bits have nothing to do with the output voltage.
MSB: Most significant bit
LSB: Least significant bit
The following graph shows the current output characteristics of the Analog Out-
put Unit.
Output current (mA)
20
10
0
Output data (hexadecimal)
0000 0400 07FF
Functions
Section 2-2