Output Circuits
TCj01/TCj03 TCj02/TCj04
The +DC terminals for NPN outputs are internally connected.
The 0V terminals for NPN outputs are internally connected.
Heater burnout alarm outputs (HB1 and HB2) are latched outputs, i.e., they will
not reset by themselves.
2-6 Application
The Unit will be in Auto Mode in STOP status when the power supply is turned
ON. An operation control command must be executed to start actual operation.
Refer to 2-6-2 Using Operation Control Commands for details on the com-
mands.
2-6-1 Communications Procedure
The following diagram illustrates the procedures used to set parameters, moni-
tor data, and read data.
Note No commands are set at startup.
Output
word
Input
word
Power ON
Initialization
Read data
Initialization
completed
FFFF
0000
Cjjj
Cjjj
Write data
60 ms max. 60 ms max.
(1) (2) (3) (4)
1, 2, 3... 1. Output word: An I/O allocation command (Cjjj) is set to specify the loop
and the items to be set and monitored.
2. Input word: The I/O allocation command set in the output word will be set by
the system as a Command Acknowledged Flag to indicate that the com-
mand has been acknowledged.
3. Output word: The write data for the I/O allocation command set in 1. is set.
4. Input word: After the data specified in 3. has been set, the data specified to
be monitored in 1. will be set by the system. This also functions as a Write
Completed Flag to indicate that the write operation has been completed.
Application
Section 2-6