246
C
Item To Be Set Item To Be Monitored
Output word
Loop number: 1 to 4
Value Item to be set Value Item to be monitored
0 Set point 0 Set point
1 Proportional band (for advanced PID) 1 Proportional band (for advanced PID)
2 Integral time (for advanced PID) 2 Integral time (for advanced PID)
3 Derivative time (for advanced PID) 3 Derivative time (for advanced PID)
4 Hysteresis (for ON/OFF control) 4 Hysteresis (for ON/OFF control)
5 Control cycle (for advanced PID or manual
control)
5 Control cycle (for advanced PID or manual
control)
6 Input shift value 6 Input shift value
7 No item set (See note 2.) 7 Process value
8 Manual manipulated variable 8 Manipulated variable
9 Do not set. 9 Status
A Heater burnout alarm setting (only for models with
heater burnout alarms)
A Heater burnout alarm setting (only for models with
heater burnout alarms)
B Do not set. B Heater current (only for models with heater
burnout alarms)
Note 1. A setting error will be indicated by outputting EE01 to the input word if any
values other than those listed above are specified. Reset the contents of the
output word if an error occurs.
2. When there is no item to set, set C7jj into the output word and then use
0000 as the write data.
3. If the write data is set before the response confirming acknowledgement of
the I/O allocation command has been received, the set value will be used for
the previous I/O allocation command. Always confirm that the I/O allocation
command has been acknowledged before setting the write data.