213
7-3-6 Scaling Value Teach
This command can be used only when the timing hold in operation mode A is set
to normal.
This command is used to execute scaling value teaching. When scaling value
teaching is executed, the present input value can be used as the X1 or X2 scal-
ing value.
Command
Command Code
Teaching scaling value
0: X1
1: X2
Parameter Parameters are not used with this command.
Response
If the wrong command code is set to the output word, the following error code will
be set to the input word.
E000: This error code will be set to the input word if a nonexisting command code
is used.
E002: Teaching command execution error
E003: This error code will be set to the input word if the mode designation for this
command is not correct.
7-3-7 Scaling Value Read
This command is used to read a scaling value.
Command
Command Code
Scaling value
0: X1
1: X2
2: Y1
3: Y2
Parameter Parameters are not used with this command.
Response
If the output word is set to the correct command code, the sign of the scaling val-
ue and the scaling value will be set to the input word alternately in the following
format.
Sign
0: Positive
F: Negative
Value
Range: 0 to 9999
Factory-set values:
X1 = 0, X2 = 1000,
Y1 = 0, and Y2 = 1000
Commands and Responses
Section 7-3