151
4. Move the object to the position where you want the output ON and press the
teaching button. If teaching is successful, the teaching indicator will turn
from orange to green.
ȏ
5. Do not move the sensing object and press the teaching button a third time. If
teaching is successful, the teaching indicator will turn from green to orange.
ȏ
6. Set the mode selector to RUN to complete the sensitivity setting on the E3X-
MA11. If teaching is unsuccessful, the teaching indicator (orange) will flash,
in which case make sure that the sensor cable is connected, change the
position of the object and the sensing distance that have been set, and re-
peat from step 3.
ON point
ȏ
Note Teach within the stable sensing range. Although indicators may indicate that
teaching is OK even outside of this range, the sensor may not reset properly af-
ter detection. Always check to be sure the sensor is resetting after teaching.
Operation without CQM1-TU001 Remote Console Section 4-1