171
The Unit needs zero input and zero reset input for forced zero.
The CQM1-LSE01 does not have monitor output.
Word Number The word allocations for a CQM1H/CQM1-series Dedicated I/O Unit are as fol-
lows.
Input: 001 to 015
Output: 100 to 115
The Unit uses a single input word and single output word. The CQM1-LSE01,
which is not provided with the monitor output function, also uses a single output
word.
Words are allocated in left-to-right order to the CQM1H/CQM1-series Dedicated
I/O Units mounted to the PC. For example, if an Input Unit that occupies one
word, an Output Unit that occupies two words, and the CQM1-LSE01/LSE02 are
mounted to the PC and if the Input Unit and Output Unit are located to the left of
the CQM1-LSE01/LSE02, the input and output word numbers of the
CQM1-LSE01/LSE02 will be 002 and 102 respectively.
to
to
Input word
Output word
Input Unit located on the left side
CPU
Output Unit located
on the left side
CQM1-LSE01/LSE02
System Configuration
Section 1-2