Refer to the following table for the ON and OFF conditions of the flags for the
comparison results.
ON OFF
HH
Scaled conversion data y HH set
value
Scaled conversion data < HH set
value – hysteresis
H
Scaled conversion data y H set
value
Scaled conversion data < H set
value – hysteresis
L
Scaled conversion data x L set
value
Scaled conversion data > L set
value + hysteresis
LL
Scaled conversion data x LL set
value
Scaled conversion data > LL set
value + hysteresis
PASS HH, H, L, and LL set values turned
OFF
HH, H, L, or LL set values turned
ON
If the Unit receiving 1- to 5-V or 4- to 20-mA input detects sensor disconnection,
the Sensor Disconnection Flag will be ON and all the Comparison Result Flags
will be OFF.
If input to the Unit is not within the permissible input range, the Overrange Flag
will be ON. The status of each Comparison Result Flags will remain unchanged.