47
Additional Unit Mounted Between Master and Expansion Master or Be-
tween Two Expansion Masters
Take care of the allocation of Expansion Master word addresses.
I/O Output
Master
Expansion Master
Unit 1
Expansion Master
Unit 2
Unit
Input word
Output
word
Input
16
points
16
points
16
points
CQM1H/CQM1
Master of Another System is Mounted Between the Master and Expansion
Master or Between Two Expansion Masters of a System
Take care that the transmission cables of System 1 and System 2 are not wired
together. Each system must be wired separately.
System 1
I/O Output
Master
Expansion Master
Unit 1
Expansion Master
Unit 2
Unit
Input word
Output
word
Input
16
points
16
points
System 1
System 2
Master
CQM1H/CQM1
4-1-3 G730 Remote Terminal Allocation
Slave Address Allocation Using one Master and two Expansion Masters in one system allows the connec-
tion of up to 28 Slaves (G730 Remote Terminals).
Use the DIP switch to set the Slave address for each Slave to a value from #0 to
#27. Addresses #24 to #27 cannot be set for 4-point Slaves. The Master and
Expansion Masters recognize the controlled Slave by the Slave address.
Word Allocation Section 4-1