71
Remote I/O Allocations Section 3-2
Note (1) Turns OFF when one of the errors shown in 7-3 Error History occurs.
(2) For information on errors, refer to 7-2 Troubleshooting.
(3) Safety input data is not the data directly from the safety input terminals,
but rather it is the value after input evaluation (input device and input cir-
cuit diagnosis, input ON/OFF delays, and dual channel evaluation).
Data Description
Input data General Status Data DST1-ID12SL-1
DST1-MD16SL-1
DST1-MRD08SL-1
DST1-XD0808SL-1
Bit 0 Safety Input Power Status Flag
0: Input power supply ON
1: Input power supply OFF
Bit 1 Safety Output Power Status Flag
0: Output power supply ON
1: Output power supply OFF
Bit 2 Network Power Voltage Drop Flag
0: Normal (higher than set monitor value)
1: Error (same as or lower than set monitor value)
Bit 3 Unit Maintenance Flag
0: Within range (lower than set monitor value)
1: Over range (same as or higher than set monitor value)
Bit 4 Reserved Operating Mode Flag
0: Not RUN mode
1: RUN mode
Bit 5 Combined I/O Port Status Flag
0: Normal (all I/O points normal)
1: Error (one or more I/O point error)
Bit 6 Operation Time Exceeded Flag
0: Within range (all I/O values are
lower than set monitor value)
1: Over range (one or more value is
same as or higher than set value)
Status Flag
0: Error (See note 1.)
1: Normal
Bit 7 Connected Component Maintenance Flag
0: Within range (all I/O points are lower than set monitor value)
1: Over range (one or more I/O point is same as or higher than set monitor
value)
Output data Safety Output Data
SAFE
Controls the safety output terminal.
0: OFF
1: ON
Safety Output Data and Output
Condition Signal (DST1-
XD0808SL-1 only)
SAFE
When the safety output terminal is set to Output from network:
Safety output terminal ON/OFF status
0: OFF
1: ON
When the safety output terminal is set to Output from internal logic:
Remote I/O signal for output condition operation
0: OFF
1: ON
Output Condition Signal (DST1-
XD0808SL-1 only)
Remote I/O signal for output condition operation
When the safety output terminal is set to Output from internal logic:
0: OFF
1: ON
Standard Output Data Controls the test output when test output mode is set to a standard output.
0: OFF
1: ON
Input Condition Signal (DST1-
XD0808SL-1 only)
SAFE
Input condition signal for safety inputs. Used for input condition operations.
0: OFF
1: ON
Reset Signal (DST1-XD0808SL-1
only)
Reset signal for safety inputs. Used for reset operations.
0: OFF (Low)
1: ON (High)