6 - 67
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Advanced Function Setting Level
6
st-b
ST Stable Range
Temperature input, standard control, 2-PID control
must be set.
The ST parameter must be set to ON.
The setting of this parameter determines when ST operates.
This parameter cannot be used when ST is set to OFF.
Related Parameters
Input Type (Initial Setting Level): Page 6-43
PID ON/OFF (Initial Setting Level): Page 6-45
ST (Initial Setting Level): Page 6-46
alfa
α
2-PID control must be set.
The ST parameter must be set to OFF.
Normally, use the default for this parameter.
This parameter sets the 2-PID control a constant.
Related Parameters
PID ON/OFF (Initial Setting Level): Page 6-45
ST (Initial Setting Level): Page 6-46
tidu
Integral/Derivative Time Unit Control must be set to 2-PID control.
This parameter sets the time unit for the Integral Time, Integral Time (Cooling), Derivative
Time, and Derivative Time (Cooling) parameters.
Note: The Integral/Derivative Time Unit parameter changes to 0.1 when the RT (robust tuning)
parameter is changed from OFF to ON.
Related Parameters
Integral Time and Derivative Time (Adjustment Level): Page 6-28
Derivative Time (Cooling) and Integral Time (Cooling) (Adjustment Level): Page 6-29
Function
Setting
Setting range Unit Default
0.1 to 999.9 °C or °F 15.0
See
See
Function
Setting
Setting range Default
0.00 to 1.00 0.65
See
See
Function
Setting
Setting range Unit Default
1 to 0.1 Seconds 1
See
See