6 - 95
6 Parameters
E5@C-T Digital Temperature Controllers User’s Manual (H185)
6-10 Advanced Function Setting Level
6
This parameter enables or disables the LBA function and sets the detection time interval.
hsh
HS Alarm Hysteresis
HB and HS alarms must be supported.
The HS Alarm Use parameter must be set to ON.
The HS Alarm Latch parameter must be set to OFF.
• This parameter sets the hysteresis for HS alarms.
z Related Parameters
HS Alarm Use (Advanced Function Setting Level): Page 6-94
lba
LBA Detection Time
A Standard Model must be used.
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
ON/OFF control must be used.
• To disable the LBA function, set 0.
z Related Parameters
Alarm 1 to 4 Type (Initial Setting Level): Page 6-66
LBA Level (Advanced Function Setting Level): Page 6-96
LBA Band (Advanced Function Setting Level): Page 6-96
Function
Setting
Setting range Unit Default
0.1 to 50.0 A 0.1
See
See
Function
Setting
Setting range Unit Default
0 to 9999 Seconds 0
See
See

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals