EasyManuals Logo

Omron E5*C Series User Manual

Omron E5*C Series
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #361 background imageLoading...
Page #361 background image
6 Parameters
6 - 100
E5@C-T Digital Temperature Controllers User’s Manual (H185)
sptr
SP Tracking
• This parameter sets the operation to perform when moving from Program SP Mode to
Fixed SP Mode.
• When this parameter is turned ON, operation continues using the program SP as the
fixed SP.
• When this parameter is OFF, the fixed SP is not affected by the program SP.
z Related Parameters
SP Mode (Adjustment Level): Page 6-28
pidi
pidh
PID Set Automatic Selection Data
PID Set Automatic Selection
Hysteresis
Control must be set to 2-PID control.
• These parameters set data for automatic selection of the PID set.
• The PID set number to use is automatically selected according to the values set for the
PID Set Automatic Selection Data parameter. The change range is specified in the PID
Set Automatic Selection Range Upper Limit parameter.
• The PID Set Automatic Selection Hysteresis parameter sets hysteresis to prevent
chattering when changing the PID set.
z Related Parameters
PID * Automatic Selection Range Upper Limit (PID Setting Level): Page 6-49
PID Set No. (PID Setting Level): Page 6-20
Function
Setting
Setting range Default
on: Enabled or off: Disabled off
See
See
Function
Setting
Parameter Setting range Unit Default
PID Set Automatic Selection Data pv: PV
dv: Deviation
sp: SP
--- pv
PID Set Automatic Selection Hysteresis 0.10 to 99.99 %FS 0.50
See
See

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals