EasyManua.ls Logo

Omron E5AN-H

Omron E5AN-H
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
188
Operation Level Section 5-3
Related Parameters
Input type: Page 224, Scaling upper limit, Scaling lower limit, Decimal point:
Page 226, Alarm 2 type: Page 233 (initial setting level), Standby sequence
reset: Page 244, Auxiliary output * open in alarm: Page 245, Alarm 2 hystere-
sis: Page 233, Alarm 2 latch: Page 250 (advanced function setting level)
Bank * alarm value upper limit 2, Bank * alarm value lower limit 2 (bank setting
level): Page 213
These parameters independently set the alarm value upper and lower limits
when the mode for setting the upper and lower limits is selected for the Alarm
3 Type parameter (initial setting level).
This parameter sets the upper and lower limit values of alarm 3.
During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the Decimal
Point parameter setting.
The set value is saved in the Alarm Value Upper Limit 3 and Alarm Value
Lower Limit 3 parameters in the current bank.
Related Parameters
Input type: Page 224, Scaling upper limit, Scaling lower limit, Decimal point:
Page 226, Alarm 3 type: Page 234 (initial setting level), Standby sequence
reset: Page 244, Auxiliary output * open in alarm: Page 245, Alarm 3 hystere-
sis: Page 233, Alarm 3 latch: Page 250 (advanced function setting level)
Bank * alarm value upper limit 3, Bank * alarm value lower limit 3 (bank setting
level): Page 214
This parameter is used to check the manipulated variable for the heating con-
trol output during operation.
This parameter cannot be set.
During standard control, the manipulated variable is monitored. During
heating/cooling control, the manipulated variables on the control output
(heating) is monitored.
The default is OFF and the manipulated variable is not displayed.
See
See
al3h Alarm Value Upper Limit 3
Alarm 3 must be assigned.
The alarm 3 type must not be 1, 4, or
5.
al3l Alarm Value Lower Limit 3
Setting range Unit Default
1999 to 9999 EU 0
Function
Setting
See
See
o MV Monitor (Heating)
The MV Display parameter must be
set to ON.
Control Monitor range Unit
Standard 5.0 to 105.0 %
Heating/cooling 0.0 to 105.0 %
Function
Monitor

Table of Contents

Other manuals for Omron E5AN-H

Related product manuals