Section 8 Setting data
8-44
Setting data
The setting range is 0 to 1 on a single- or 4-input type, or 0 to 6 on a 2-
input type.
Related information
"Section 3 Typical Control Examples" (P. 3-1)
"4.6 Selecting the control mode" (P.4-13)
Related setting data
"Manual reset value" (Adjustment level) (P.8-15)
"Hysteresis (heat)", "Hysteresis (cool)" (Adjustment level) (P.8-16)
"Control/Transfer output
assignment" (Control initial setting 2 level)
(P.8-46)
When direct action is selected, the MV is increased when the PV
increases. When reverse action is selected, the MV is increased
when the PV decreases.
Related information
"4.7 Setting output parameters Direct operation (cool) / Reverse
operation (heat)" (P.4-14)
Use this setting to select the control method for a position propor-
tional type.
Related information
"3.3 Position proportional control of a ceramic kiln" (P.3-9)
Setting
Setting range Units
Default value
0: Standard
1: Heating/cooling
2: Remote SP standard
3: Remote SP heating/cooling
4: Proportional
5: Cascade standard
6: Cascade heating/cooling
0
Reference
Reference
Forward/reverse operation
orev
CH
l.1
Function
Setting
Setting range Units Default value
or-r: Reverse operation
or-d: Direct operation
or-r: Reverse action
Reference
Reference
Closed/Floating
clfl
Position proportional type
CH
l.1
Function
Setting
Setting range Units Default value
float: Floating
close: Closed
float: Floating
Reference
Reference