Grid Connect Photovoltaic Inverte KP100L-OD-USER’S MANUAL
Solar Module
Do not connect the solar module that has an open-circuit voltage in excess of 850 VDC.
Do not connect the solar module that require earthing of negative or positive pole.
Breaker
Use the breaker that corresponds to the capacity of the solar modules for the breaker of the Solar modules
side.
Use the 20A trip breaker with B or C or D trip characteristics for the breaker of the grid side.
Maintenance - Inspection
Be sure to inspect install condition, wiring connection, before doing a trial operation.
To secure the IP65 performance, execute the additional tightening of the cable clamp regularly.