1 Overview
1 - 8
Grid Connect Photovoltaic Inverte KP100L-OD-USER’S MANUAL
Photo-Coupler Input
The KP100L has the photo-coupler for input signals of the table below. Refer to"3-5 Parameter List" for the
setting of the input signal.
[Example when you use AUX_IN]
Name Type of contact Specifications
AUX_IN Photo-Coupler
10mA Use 24 VDC to use AUX_IN.
Minimum ON time : 100ms
Leakage current at OFF status 0.1mA
Residual voltage at ON status 2.0V
Capacity of external switch 20mA
1234 56 78910
AUX_OUT1 AUX_OUT2
AUX_IN
24VDC
AUX Terminal Block
10mA
KP100L