2 Design
2 - 4
Grid Connect Photovoltaic Inverte KP100L-OD-USER’S MANUAL
Applicable solar module
The KP100L is designed to control the voltage of negative pole on solar module as same voltage level as Neutral
of grid as shown in figure below. This can be achieved by new inverter circuit (ZCC).
As a result, the voltage of negative pole on solar module is approx. zero. According to this function, you can use
the solar module which does not allow negative voltage on solar module.
Do not use the solar module that require earthing of negative or positive pole. Otherwise, the failure might occur.
Applicable type of solar module is shown in the table below.
Solar module manufacture
requirement
Type of solar module Applicable or not
(1) No requirement
Conventional silicon-based solar
modules
KP100L can be used.
(2) No negative voltages on solar
module
Some thin-film or silicon modules Basically, KP100L can be used.
(3) Earthing of negative pole on
solar module
Some thin-film or silicon modules KP100L can not be used.
(4) No positive voltages on solar
module
Specific solar module KP100L can not be used.
(5) Earthing of positive pole on
solar module
Specific solar module KP100L can not be used.
U
SG
0
Voltage of solar module
The voltage of the negative
pole is controlled as same
voltage level of Neutral.
Solar module
+
-
Solar module
+
-
Note: Dec,2010
KP100L does not have the compatibility with thin-film module at this moment.
The compatibility is under evaluation.