Cat.No. V043–E1–2
Programmable Terminal
NT31/31C
OPERATION MANUAL

Table of Contents

Other manuals for Omron NT31

Questions and Answers

  • H
    Helen HarrellSep 16, 2025
    What does '[Tool Transmit Error] Check Sum Error occurs while downloading' mean on Omron NT31 Touch terminals?
    • K
      knappcherylSep 16, 2025
      If your Omron Touch terminal displays the message '[Tool Transmit Error] Check Sum Error occurs while downloading', it might be due to malfunction caused by external noise. Carry out grounding work.
  • M
    Michael BellSep 12, 2025
    What does '[Screen Data Error] Screen Data corrupted. Initialize Screen Memory, and download Screen Data again' mean on Omron Touch terminals?
    • N
      Nicole PerezSep 12, 2025
      If your Omron Touch terminal displays the error message '[Screen Data Error] Screen Data corrupted. Initialize Screen Memory, and download Screen Data again,' it indicates that the power was switched OFF during screen data initialization, checking, or transmission; transmission of screen data was interrupted; or illegal data has been written to the screen data memory. Initialize the screen data memory by operation at the System Menu, then re-transmit the screen data. If the problem persists, contact your OMRON service center.
  • S
    sara55Sep 9, 2025
    Why cannot switch screens with touch switches on Omron NT31 Touch terminals?
    • M
      Michael FitzpatrickSep 9, 2025
      If you cannot switch screens with touch switches on your Omron Touch terminal, it might be because bit 4 of the PT status control area (PT screen switching) is set to 1 (ON). Set bit 4 to 0 (OFF).
  • N
    Nathan HowardAug 29, 2025
    How to enable System Menu on Omron Touch terminal?
    • G
      golsonAug 29, 2025
      If the System Menu cannot be called up on your Omron Touch terminal, Display System Menu under Change System Settings in the System Installer mode might be set to Disabled. In the System Installer mode, set Display System Menu to Enabled.
  • R
    Russell LeeAug 29, 2025
    Why can't I input numeric values on my Omron Touch terminal?
    • L
      lrussellAug 29, 2025
      If you cannot input numeric values on your Omron Touch terminal, the upper/lower (max./min.) limit check for numeric value input might be in effect. Check the screen data’s upper/lower (max./min.) limit check setting for numeric value input, and correct it if necessary.
  • C
    craigrobinsonAug 29, 2025
    Why can't I input numeric values or character strings on my Omron Touch terminal?
    • S
      Steven MartinezAug 29, 2025
      If you cannot input numeric values/character strings on your Omron Touch terminal, bit 5 of the PT status control area (numeral/character string input) might be set to 1 (ON), or the interlock function is set for the input field and the controlling interlock bit is OFF. Set bit 5 to 0 (OFF). Inputs are prohibited in input fields when the corresponding interlock bit is OFF. Check the status of the corresponding interlock bit and turn it ON.
  • C
    Christopher StewartAug 29, 2025
    Why is the window screen not opening on my Omron Touch terminal?
    • S
      stephanie09Aug 29, 2025
      If the window screen does not open on your Omron Touch terminal, bit 6 of the PT status control area (PT window opening) might be set to 1 (ON). Set bit 6 to 0 (OFF).
  • A
    albert05Sep 23, 2025
    What does '[Memory Switch Corrupted]' mean on Omron NT31 Touch terminals and how can I solve it?
    • R
      rodriguezmelindaSep 23, 2025
      The '[Memory Switch Corrupted]' message on your Omron Touch terminals indicates that the memory switches have been initialized due to discovery of an error in the memory switch settings. Set the memory switches again using the System Menu and the “System” settings under “PT Configuration” at the Support Tool.
  • K
    Kevin SmithSep 23, 2025
    What does '[Programming Console Error]' mean on Omron NT31 Touch terminals and how can I fix it?
    • T
      taylorpeterSep 23, 2025
      The '[Programming Console Error]' message on your Omron Touch terminals means that the communication settings are incorrect. Set the communication method/communication port as follows when using the programming console function: With C series PLC, use NT Link : 1 : 1; with CS1 series PLC, use NT Link : 1 : N.
  • J
    Joseph BrownSep 12, 2025
    What does '[No Comm. Protocol] Set the comm. Protocol by MAINTENANCE MODE' mean on Omron NT31 Touch terminals?
    • T
      Tyrone MartinSep 12, 2025
      If your Omron Touch terminal displays the message '[No Comm. Protocol] Set the comm. Protocol by MAINTENANCE MODE', it indicates that no communication protocol has been set, or the communication protocol and screen data type are mismatched. Using the memory switches, set the communication method to be used for communication with the host.

Omron NT31 Specifications

General IconGeneral
Display TypeSTN LCD
Touch PanelAnalog resistive
Communication InterfaceRS-232C, RS-422/485
Power Supply24 VDC
Operating Temperature0 to 50 °C
Storage Temperature-20 to 60 °C
Display Size5.7 inch
Resolution320 x 240 pixels
CPU32-bit RISC
Humidity10 to 90% RH (non-condensing)
Shock Resistance15 G for 11 ms
Protection classIP65 (front panel)