9-9
9 Details on Servo Parameter Objects
G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
9-2 Gain Settings
9
Set the time constant for the low pass filter (LPF) after speed detection to one of 6 levels (0 to 5).
Increasing the set value increases the time constant and decreases the noise generated by the
motor. Responsiveness, however, also decreases.
Normally, use the default set value.
*1 The default setting is 126 for a Drive with 200 V and 1 kW or greater, or with 400 V.
Set the time constant for the first-order lag filter inserted into the torque command.
This object may be effective in suppressing vibration due to torsion resonance.
*1 The default setting is 380 for a Drive with 200 V and 1 kW or greater, or with 400 V.
Set the responsiveness of the position control system for the second position loop.
*1 The default setting is 180 for a Drive with 200 V and 1 kW or greater, or with 400 V.
Set the responsiveness of the second speed loop.
Set the second speed loop integral time constant.
Set the second speed feedback filter.
3103 hex
Speed Feedback Filter Time Constant 1
Setting range 0 to 5 Unit
Default setting
0 Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3104 hex
Torque Command Filter Time Constant 1
Setting range 0 to 2500 Unit 0.01 ms
Default setting
84
*1
Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3105 hex
Position Loop Gain 2
Setting range 0 to 30000 Unit 0.1/s
Default setting
570
*1
Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3106 hex
Speed Loop Gain 2
Setting range 1 to 32767 Unit 0.1 Hz
Default setting
270
*1
Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3107 hex
Speed Loop Integral Time Constant 2
Setting range 1 to 10000 Unit 0.1 ms
Default setting
10000 Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3108 hex
Speed Feedback Filter Time Constant 2
Setting range 0 to 5 Unit
Default setting
0 Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
All
All
csp
pp
hm
All
All
All