11-33
11 Adjustment Functions
G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
11-11 Feed-forward Function
11
11-11-2 Operating Procedure
1
Set the Inertia Ratio (3004 hex).
Set the inertia ratio as correctly as possible.
• If the inertia ratio is calculated for the selected motor, input the calculated value.
• If the inertia ratio is not known, perform autotuning and set the inertia ratio.
2
Set the Torque Feed-forward Command Filter (3113 hex).
Set it to approx. 50 (0.5 ms).
3
Adjust the Torque Feed-forward Gain (3112 hex).
Gradually increase the value of the Torque Feed-forward Gain (3112 hex).
Since the position error during acceleration/deceleration at a constant speed can be brought
close to 0, it can be controlled almost to 0 throughout the entire operation range during a
trapezoidal speed pattern under ideal conditions where no disturbance torque is working.
In reality, disturbance torque is always applied and, therefore, the position error cannot be
completely 0.
Torque feed-forward can reduce the position error in a range of constant acceleration/
deceleration.
Precautions for Correct UsePrecautions for Correct Use
• If you increase the torque feed-forward filter time constant, the operation noise will be reduced.
However, the position error where the acceleration changes will become larger.
• The torque feed-forward function cannot be used when realtime autotuning is being used. Set
both the Torque Feed-forward Gain (3112 hex) and Torque Feed-forward Command Filter
(3113 hex) to 0.
Torque Feed-forward Operating Method
Command
speed
Motor speed
Position error
Speed Feed-forward Gain = 100 [%] (fixed)
100
[%]
0
[%]
Torque
Feed-forward Gain
50
[%]
Time