12 Troubleshooting and Maintenance
12-20
G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
29 1 Error Counter
Overflow 1
The value that is obtained by dividing the
absolute encoder position (in pulses) by the
electronic gear ratio exceeded ±2
31
(2,147,483,648) during the initialization of
position data, after the control power was
turned ON in absolute value mode, after a
Config operation, after FFT was executed, or
after a trial run was executed.
Review the operation range of the absolute
external encoder position and the electronic
gear ratio.
2 Error Counter
Overflow 2
The position error in pulses exceeded
±2
29
(536,870,912). Alternatively, the
position error in command units exceeded
±2
30
(1,073,741,824).
Check to see if the Servomotor rotates
according to the position command.
Check on the torque monitor to see if the
output torque is saturated.
Adjust the gain.
Maximize the set values on the Positive
torque limit value (60E0 hex) and the
Negative torque limit value (60E1 hex).
Wire the encoder as shown in the wiring
diagram.
30
(st)
0 Safety Input
Error
At least one of the input photocouplers for
safety inputs 1 and 2 turned OFF.
Check the input wiring of safety inputs 1
and 2.
33 0 Interface
Input
Duplicate
Allocation
Error 1
There is a duplicate setting in the input
signal (IN1, IN2, IN3, and IN4) function
allocations.
Allocate the functions to the connector pins
correctly.
1 Interface
Input
Duplicate
Allocation
Error 2
There is a duplicate setting in the input
signal (IN5, IN6, IN7, and IN8) function
allocations.
2 Interface
Input
Function
Number
Error 1
There is an undefined number specification
in the input signal (IN1, IN2, IN3, and IN4)
function allocations. Alternatively, a logic
setting error was detected.
3 Interface
Input
Function
Number
Error 2
There is an undefined number specification
in the input signal (IN5, IN6, IN7, and IN8)
function allocations. Alternatively, a logic
setting error was detected.
4 Interface
Output
Function
Number
Error 1
There is an undefined number specification
in the output signal (OUTM1) function
allocation.
5 Interface
Output
Function
Number
Error 2
There is an undefined number specification
in the output signal (OUTM2) function
allocation.
8External
Latch Input
Allocation
Error
There is an error in the latch input function
allocation.
The function was allocated to input signals
other than IN5, IN6, or IN7.
The function was allocated to NC.
The function was not allocated for all
control modes.
Error No. (hex)
Name Cause Measures
Main Sub
ABS