12 Troubleshooting and Maintenance
12-28
G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
Error number
Name
Error
timing
Cause Measures
Main Sub
90 0 Communica
tions setting
error
Occurs
when the
power
supply is
turned ON.
An out-of-range value was set from
the host controller.
A command that changes the
communications state to an
unsupported state was received.
Make EtherCAT communications
settings such as the synchronous
cycle (SYNC0 cycle) correctly.
Check the specifications of the
communications state change
command for the host controller.
91 1 Command
error
Occurs
during
operation.
When bit 9 (Remote) of the
Statusword (6041 hex) was set to 1
(remote), and the Servo Drive was
in operation enabled state (Servo
ON), a command that changes the
communications state from
Operational to another state (Init,
Pre-Operational, Safe-Operational)
was received.
An unsupported number was set in
Modes of operation (6060 hex).
CSV or CST was set in Modes of
operation (6060 hex) during fully-
closed control.
The Modes of operation (6060 hex)
was switched in less than 2 ms.
The homing operation was started
when the Homing method
(6098 hex) was set to a value other
than 8, 12, 19, 20, 33, 34, or 35.
The data setting warning (Warning
No. B0 hex) occurred in a row,
exceeding the Data Setting
Warning Detection Setting
(3781 hex) value.
Check the command specifications of
the host controller.