• This object enables changing objects with data attribute C.
• This function can be executed by writing 666e 6f63 hex using SDO mailbox communications.
• The Servo will be forced OFF if Configuration is executed in the Servo ON state.
• The Servo Drive moves to a Fault state (Error No. 27.7) after this process is completed.
• In the following cases, an ABORT code is returned.
Writing with CompleteAccess.
Writing a value other than 666e 6f63 hex.
Writing when there is a Control Power Supply Undervoltage Error (Error No. 11.0).
• This object clears the multi-rotation counter of the absolute encoder.
• This function can be executed by writing 6a64 6165 hex using SDO mailbox communications.
• The Servo Drive moves to a Fault State (Error No. 27.7) after this process is completed.
Cycle the control power supply to the Servo Drive.
• In the following cases, an ABORT code is returned.
Writing with CompleteAccess.
Writing a value other than 6a64 6165 hex.
Writing during semi-closed control when using an absolute encoder as an absolute encoder and the
Servo is not OFF.
• Set the mode during coordinate system setting.
• Set the position information during coordinate system setting.
• This object resets errors and warnings.
• This function can be executed by writing 7473 7274 hex using SDO mailbox communications.
4100 hex
Config
Range 0000 0000 to
FFFF FFFF hex
Unit − Default 0000 0000 hex Attribute A
Size 4 bytes (U32) Access RW PDO map Not possible
4102 hex
Absolute Encoder Setup
Range 0000 0000 to
FFFF FFFF hex
Unit − Default 0000 0000 hex Attribute A
Size 4 bytes (U32) Access RW PDO map Not possible
4103 hex
Coordinate System Setting Mode
Range 0000 to
FFFF hex
Unit − Default 0 Attribute B
Size 2 bytes (U16) Access RO PDO map Possible
4104 hex
Coordinate System Setting Position
Range
−
2,147,483,648 to
2,147,483,647 hex
Unit Command
units
Default 0 Attribute B
Size 4 bytes (INT32) Access RO PDO map Possible
4107 hex
Error Reset
Range
0000 0000 to
FFFF FFFF hex
Unit − Default 0000 0000 hex Attribute A
Size 4 bytes (U32) Access RW PDO map Not possible