CompoWay/F Communications Specifications Section 6-1
6-1 CompoWay/F Communications Specifications
The S8AS-@@@@@R is equipped with an RS-485 port, which allows remote
monitoring and remote operations over networks, such as setting parameters,
connecting/disconnecting outputs, and clearing errors.
Connecting to the
Network
Refer to 3-4 RS-485 Port Wiring for details on connecting the communications
cable.
Communications
Specifications
Communications cable
Connection configuration 1:n connection
Communications method RS-485
Synchronization method Start-stop synchronization
Baud rate 4,800 or 9,600 bps (Default value: 9,600 bps)
Transmission code ASCII
Data length 7 or 8 bits (Default value: 7 bits)
Stop bits 1 or 2 bits (Default value: 2 bits)
Error detection Vertical parity: None, even, or odd (Default value: Even)
BCC (block check character)
Flow control None
Retry function None