109
Response Code List Section 6-9
6-9 Response Code List
Response
code
Error name Cause Error
priority
0000 Normal completion No error
0401 Unsupported com-
mand
The service function for the
specified command is not sup-
ported.
1
1001 Command too long The command is too long. 2
1002 Command too short The command is too short. 3
1101 Area type error The variable type is incorrect. 4
1003 Number of elements/
data mismatch
The amount of data does not
match the number of elements.
5
100B Response too long The response exceeds the com-
munications buffer size.
6
1100 Parameter error The bit position is not 00.
A value that must be 00 was
not set to 00.
Incorrect command code or
related information in the oper-
ation command.
Incorrect operating mode or
related information in a change
operating mode command.
The write data is out of the set-
ting range.
7
3003 Read-only error Attempted to write a read-only
variable.
8
2203 Operation error The operation command could
not be processed.
Not moved to system search
mode.
A non-volatile memory error
occurred.
Executed within 15 seconds
after the last reset operation.
9