7-6
Fault
display
Probable cause and remedyFault name and
meaning
f04 Initial memory fault
(F04)
An error in the built-in
EEPROM of the Inverter
has been detected.
The internal circuitry of the Inverter has a fault.
Initialize the Inverter with n01 set to 8 or 9 and
turn the Inverter off and on.
Replace the Inverter if the same fault occurs
again.
f05 Analog-to-digital
converter fault (F05)
An analog-to-digital
converter fault has been
detected.
The internal circuitry of the Inverter has a fault.
Turn the Inverter off and on.
Replace the Inverter if the same fault occurs
again.
f07 Digital Operator fault
(F07)
An error in the built-in
control circuit of the
Digital Operator has
been detected.
The internal circuitry of the Digital Operator has a
fault.
Turn the Digital Operator off and on.
Replace the Digital Operator if the same fault
occurs again.
Emergency stop (STP)
An emergency stop
alarm is input to a
multi-function input. (A
multi-function input 1, 2,
3, or 4 set to 19 or 21
has operated.)
An emergency stop alarm is input to a multi-func-
tion input.
Remove the cause of the fault.
The sequence is incorrect.
Check and change the external fault input
sequence including the input timing and NO or
NC contact.
OFF Power supply error
Insufficient power sup-
ply voltage
Control power supply
fault
Hardware fault
No power supply is provided.
Check and correct the power supply wire and
voltage.
Terminal screws are loosened.
Check and tighten the terminal screws.
The Inverter is damaged.
Replace the Inverter.