5-7
5-4 Selecting the Operation Command
The following description provides information on how to input operation
commands
to start or stop the Inverter or change the direction of rotation of
the Inverter.
Two types of command input
methods are available. Select either one of
them according to the application.
H Selecting the Operation Mode (n02)
Select the method of operation mode input to start or stop the Inverter.
The following method is enabled in remote mode only. The command can be input
through key sequences on the Digital Operator.
n02 Operation Command Selection Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 The RUN and STOP/RESET Keys of the Digital Operator are enabled.
1 Multi-function input in 2- or 3-wire sequence through the control circuit
terminals is enabled.
H Selecting the STOP/RESET Key Function (n06)
When
parameter n02 is set to 1, set whether or not to use the ST
OP/RESET Key of the
Digital
Operator to stop the Inverter in remote mode. The ST
OP/RESET Key is always
enabled in local mode regardless of the setting in n02.
n06 STOP Key Function Selection Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 The STOP/RESET Key of the Digital Operator is enabled.
1 The STOP/RESET Key of the Digital Operator is disabled. This setting is
available only when the Digital Operator is selected for operation command
input.
Basic Operation Chapter
5