EasyManua.ls Logo

Omron SYSDRIVE 3G3JV Series - Page 27

Omron SYSDRIVE 3G3JV Series
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-19
H Wiring on the Input Side of the Main Circuit
D Installing a Molded-case Circuit Breaker
Always
connect the power input terminals (R/L1, S/L2, and T/L3) and power supply via a
molded case circuit breaker (MCCB) suitable to the Inverter.
Choose an MCCB with a capacity of 1.5 to 2 times the Inverter’s rated current.
For the MCCB’s time characteristics, be sure to consider the Inverter’s overload
protection (one minute at 150% of the rated output current).
If
the MCCB is to be used in common among multiple Inverters, or other devices, set up
a
sequence such that the power supply will be turned of
f by a fault output, as shown in
the following diagram.
3-phase/Single-
phase 200 VAC
Power
supply
Inverter
Fault output
(NC)
D Installing a Ground Fault Interrupter
Inverter
outputs use high-speed switching, so high-frequency leakage
current is gener
-
ated.
In
general, a leakage current of approximately 100 mA will occur for each Inverter (when
the power cable is 1 m) and approximately 5 mA for each additional meter of power
cable.
Therefore,
at the power supply input area, use a special-purpose breaker for Inverters,
which
detects only the
leakage current in the frequency range that is hazardous to hu
-
mans and excludes high-frequency leakage current.
Design Chapter
2

Table of Contents

Related product manuals