6-10
n60 Overtorque Detection Level Changes during
operation
No
Setting
range
30 to 200 (%) Unit of
setting
1% Default setting 160
Set Values
Set the parameter as percentage based on the rated Inverter current as 100%.
n61 Overtorque Detection Time Changes during
operation
No
Setting
range
0.1 to 10.0 (s) Unit of
setting
0.1 s Default setting 0.1
Set Values
Set the overtorque detection time.
The Inverter will detect overtorque when the current the same as or higher than the
detection level is output for the preset detection time.