6-10
n60 Overtorque Detection Level Changes during
operation
No
Setting
range
30 to 200 (%) Unit of
setting
1% Default setting 160
Set Values
Set the parameter as percentage based on the rated Inverter current as 100%.
n61 Overtorque Detection Time Changes during
operation
No
Setting
range
0.1 to 10.0 (s) Unit of
setting
0.1 s Default setting 0.1
Set Values
Set the overtorque detection time.
The Inverter will detect overtorque when the current the same as or higher than the
detection level is output for the preset detection time.
Advanced Operation Chapter
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3JV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3JV Series Specifications

General IconGeneral
ModelSYSDRIVE 3G3JV Series
CategoryInverter
Output Frequency Range0.1 to 400Hz
Frequency Range50/60Hz
Control MethodPWM Control
Overload Capacity150% for 1 minute
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Cooling MethodFan Cooling
Ambient Temperature-10 to 50°C
Operating Temperature-10 to 50°C
Storage Temperature-20°C to +65°C
Humidity90% RH or less (non-condensing)
Altitude1000m or less
Vibration5.9 m/s² or less
Braking UnitBuilt-in
CommunicationRS-485
Voltage Class200V class, 400V class
Input Voltage3-phase 200 to 240V AC, 3-phase 380 to 480V AC