n66 Slip Compensation Gain Changes during
operation
Yes
Setting
range
0.0 to 2.5 Unit of
setting
0.1 Default setting 0.0
(see note)
Note This parameter is disabled with the value set to 0.0.
Set Values
Set
the parameter to 1.0
first and check the operation of the Inverter
. Then fine-tune the
gain with 0.1-gain increments or decrements.
If the speed is lower than the target value, increase the set value.
If the speed is higher than the target value, decrease the set value.
n67 Slip Compensation Parameter Changes during
operation
No
Setting
range
0.0 to 25.5 (s) Unit of
setting
0.1 s Default setting 2.0
Set Values
This
parameter is used for the response adjustment of the slip compensation function.
The default setting does not need any changes in normal operation.
Change the default setting in the following cases.
The motor vibrates: Set the value to a larger value.
The motor response is low: Set the value to a smaller value.