5-20
5
Field Forcing: d6
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Closed
Loop
Vector
(PM)
Display
d6-03
Field forc-
ing function
selection
Enables or disables field forcing func-
tion.
0:Disabled
1:Enabled
0 or 1 0 No - A A - 2A2H 6-38
Field Force
Sel
d6-06
Field forc-
ing function
Limit
Sets the upper limit for the excitation
current applied by the field forcing
function.
A setting of 100% is equal to the
motor no-load current.
Field forcing is active during all types
of operation except DC Injection.
100 to
400
400% No - A A - 2A5H 6-38
FieldForce
Limit