5-39
5
Fault Restart: L5
L4-03
Speed agreement
detection level (+/-)
Effective when "f
out
/f
set
agree
2", "Frequency detection 3" or
"Frequency detection 4" is set
for a multi-function output.
-120.0
to
+120.0
i
No
A
0.0Hz
A
0.0Hz
A
0.0Hz
-
49BH 6-26
Spd Agree Lvl+-
-100.0
to
+100.0
-- -
A
0.0%
L4-04
Speed agreement
detection width (+/-
)
Effective when "f
ref
/f
out
agree
2" "f
out
/f
set
agree 2", "Fre-
quency detection 3" or "Fre-
quency detection 4" is set for a
multi-function output.
0.0 to
20.0
i
No
A
2.0Hz
A
2.0Hz
A
2.0Hz
-
49CH 6-26
Spd Agree Wdth+-
0.0 to
40.0%
-- -
A
4.0%
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Closed
Loop
Vector
(PM)
Display
L5-01
Number of auto
restart attempts
Sets the number of auto reset
attempts.
The auto resetable faults are:
OV, UV1, GF, OC, OL2, OL3,
OL4, UL3, UL4, PF, LF, SE1,
SE2, SE3
0 to 10 2 No A A A A 49EH 6-81
Num of Restarts
L5-02
Auto restart opera-
tion selection
Sets whether a fault contact
output is activated during fault
restart.
0:No output (Fault contact is
not activated.)
1:Output (Fault contact is acti-
vated.)
0 or 1 1 No A A A A 49FH 6-81
Restart Sel
L5-05
Under voltage fault
restart selection
Selects the reset method for a
UV1 fault.
0:UV1 fault is reset like set in
parameter L5-01
1:UV1 fault is always automat-
ically reset
0 or 1 0 No A A A A 4CCH 6-81
UV1 Restart Sel.
Param
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Closed
Loop
Vector
(PM)
Display