S2-06 Slip compensation torque detection time 0.5 sec.
S2-07 Slip compensation delay time 200 msec
S3-01 Short floor operation selection 0
S3-03 Inspection deceleration ramp time 0.0 sec.
S3-04 Nominal/Leveling speed detection level 0.0 Hz
S3-05 Nominal speed for short floor calculation 0.0 Hz
S3-06 Light load direction search for rescue operation 0
S3-07 Light load search time 1.0 sec.
S3-08 Output phase order 0
S3-09 Frequency reference missing (FRL) fault detection 1
S3-10 Light load search frequency 3.00 Hz
S3-11 Rescue operation torque limit 100%
S3-12 Base block restart selection 0
S3-13 Traction sheave diameter 400 mm
S3-14 Roping 2
S3-15 Gear Ratio 1.000
S3-16 Over acceleration detection level 1.5 m/s²
S3-17 Over acceleration deceleration time constant 0.05 sec.
S3-18 Over acceleration detection method selection 0
S3-19 Inspection speed upper limit 25.0 Hz
S3-20 Short floor minimum constant speed time 0.0 sec.
S3-21 Distance calculation acceleration time gain 150.0%
S3-22 Distance calculation deceleration time gain 150.0%
S3-24 Light load direction search method 0
T1-01 Autotuning mode selection 0
T1-02 Motor output power
*1
T1-03 Motor rated voltage
*1
T1-04 Motor rated current
*1
T1-05 Motor base frequency 60.0 Hz
T1-06 Number of motor poles 4 poles
T1-07 Motor base speed 1450 r/min
T1-08 Number of PG pulses 1024
T1-09 Motor no-load current E2-03 value
T2-01 Motor output power
*1
T2-02 Motor base frequency 1750 rpm
T2-03 Motor rated voltage
*1
T2-04 Motor rated current
*1
T2-05 Motor pole number 4
T2-08 Motor voltage constant
*1
T2-09 Number of PG pulses 2048
T2-10 Motor voltage constant calculation selection 1
*1. The factory setting depends on the inverter model and the control method.
No. Name
Factory
Setting
Setting