Comparison of high-speed counter and pulse output specifications
Item
L14 / L30
L40 / L60
High-speed counter
Single-phase 4 chs or
2-phase 2 chs
Single-phase: Max. 20 kHz
2-phase: Max. 20 kHz
Single-phase 4 chs or
2-phase 2 chs
Single-phase: Max. 50 kHz
2-phase: Max. 20 kHz
Pulse output / PWM output
Max. 1 ch
Pulse output:
Max. 20 kHz
PWM output:
Max. 1.6 kHz
Max. 2 chs
Pulse output:
Max. 20 kHz
PWM output:
Max. 1.6 kHz
Max. 2 chs
Pulse output: Max. 50 kHz
PWM output: Max. 3 kHz
Related
instructions
Trapezoidal
control
F171 (SPDH)
(Acceleration time and
deceleration time can be set
individually. Target speed cannot
be changed after the execution.)
Same as on the left.
JOG
operation
F172 (PLSH)
(Acceleration time and
deceleration time can be set
individually. Target speed cannot
be changed after the execution.)
Same as on the left.
Home return
F177 (HOME)
(Deviation counter signal cannot
be used for L14 type.)
F177 (HOME)
Linear
interpolation
Not available F175 (SPSH)
PWM output
F173 (PWMH)
Same as on the left.
Input pulse
measurement
Not available F178 (PLSM)
Note1) Typical specifications are described here. For the details of the restrictions on combinations, refer
to Chapter 7.
Comparison of software specifications
Item
L14 / L30
L40 / L60L40M / L60M
Program capacity
2.5k stpes
8k steps
Arithmetic processing speed
From 0.08µs/step
(by basic instruction)
From 0.32µs (MV instruction)
(by high-level instruction)
Up to 3000 steps:
From 0.08µs/step
(by basic instruction)
From 0.32µs (MV instruction)
(by high-level instruction)
From 3001 steps:
From 0.58µs/step
(by basic instruction)
From 1.62µs (MV instruction)
(by high-level instruction)
Operation
memory
Internal relay
1008 points
4096 points
Timer and counter
256 points
1024 points
Link relay
None
2048 points
Note1)
Data register
32765 words
32765 words
Link register
None
256 words
Note1)
MCR points
32 points
256 points
No. of labels (JP and LOOP)
100 points
256 points
No. of step ladders
128 stages
1000 stages
No. of subroutines
100 subroutines
500 subroutines
Simultaneous rewriting
capacity during RUN
Max. 128 steps Max. 512 steps
Sampling trace
None
Available
Note1) The PLC link function is available for L40M and L60M types.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP-X0 L30R and is the answer not in the manual?

Panasonic FP-X0 L30R Specifications

General IconGeneral
BrandPanasonic
ModelFP-X0 L30R
CategoryController
LanguageEnglish

Related product manuals