Function Parameters 9-25
AC10 Inverter
Table 9-4 Accel/decel selection
Accel/decel
switchover 2 (34)
Accel/decel
switchover 1 (18)
Present accel/decel time Related
parameters
0 0 The first accel/decel time F114, F115
0 1 The second accel/decel time F116, F117
1 0 The third accel/decel time F277, F278
1 1 The fourth accel/decel time F279, F280
Table 9-5 Instructions for multistage speed
K4 K3 K2 K1 Frequency setting Parameters
0 0 0 0 Multi-stage speed 1 F504/F519/F534/F549/F557/F565
0 0 0 1 Multi-stage speed 2 F505/F520/F535/F550/F558/F566
0 0 1 0 Multi-stage speed 3 F506/F521/F536/F551/F559/F567
0 0 1 1 Multi-stage speed 4 F507/F522/F537/F552/F560/F568
0 1 0 0 Multi-stage speed 5 F508/F523/F538/F553/F561/F569
0 1 0 1 Multi-stage speed 6 F509/F524/F539/F554/F562/F570
0 1 1 0 Multi-stage speed 7 F510/F525/F540/F555/F563/F571
0 1 1 1 Multi-stage speed 8 F511/F526/F541/F556/F564/F572
1 0 0 0 Multi-stage speed 9 F512/F527/F542/F573
1 0 0 1 Multi-stage speed 10 F513/F528/F543/F574
1 0 1 0 Multi-stage speed 11 F514/F529/F544/F575
1 0 1 1 Multi-stage speed 12 F515/F530/F545/F576
1 1 0 0 Multi-stage speed 13 F516/F531/F546/F577
1 1 0 1 Multi-stage speed 14 F517/F532/F547/F578
1 1 1 0 Multi-stage speed 15 F518/F533/F548/F579
1 1 1 1 None None
Note: 1. K4 is multi-stage speed terminal 4, K3 is multi-stage speed terminal 3, K2 is
multi-stage speed terminal 2, K1 is multi-stage speed terminal 1. And 0 stands for OFF, 1
stands for ON.
0=OFF, 1=ON
’s value : 0
When F326=0.0, watchdog function is invalid.
When F327=0, and during the time set by F326 elapses without an impulse being registered,
inverter will free to stop and it will trip into Err6 and digital output token is valid.
When F327=1, and during the time set by F326 elapses without an impulse being registered,
inverter will deceleration to stop, then inverter will trip into Err6 and digital output token is valid.