9-40 Function Parameters
AC10 Inverter
F724 Input phase loss
Setting range:
0: invalid;
1: valid
Mfr’s value: 1
F726 Overheat
Setting range:
0: invalid;
1: valid
Mfr’s value: 1
F727 Output phase loss
Setting range:
0: invalid;
1: valid
Mfr’s value: 0
F728 Input phase loss filtering constant
(S)
Setting range: 0.160.0 Mfr’s value: 0.5
F729 Under-voltage filtering constant (S)
Setting range: 0.160.0 Mfr’s value: 5.0
F730 Overheat protection filtering
constant (S)
Setting range: 0.160.0 Mfr’s value: 5.0
F732 Voltage threshold of under-voltage
protection (V)
Setting range: 0~450
Subject to
inverter model
“Under-voltage” refers to too low voltage at AC input side.
Input phase loss” refers to phase loss of three-phase power supply.
Output phase lossrefers to phase loss of inverter three-phase wirings or motor wirings.
·““Under-voltage” / “phase loss” signal filtering constant is used for the purpose of eliminating
disturbance to avoid mis-protection. The greater the set value is, the longer the filtering time
constant is and the better for the filtering effect.
F737 Over-current 1 protection
Setting range:
0:Invalid
1: Valid
Mfrs value: 1
F738 Over-current 1 protection coefficient
Setting range: 0.503.00
Mfrs value:
2.50
F739 Over-current 1 protection record
F738= OC 1 value/inverter rated current.
In running status, F738 is not allowed to modify. When over-current occurs, OC1 is displayed
F741 Analog disconnected protection
Setting range:
0: Invalid
1: Stop and AErr displays.
2: Stop and AErr is not displayed.
3: Inverter runs at the min
frequency.
4: Reserved.
Mfrs value: 0
F742 Threshold of analog disconnected
protection (%)
Setting range: 1~100 Mfrs value: 50
When the values of F400 and F406 are lower than 0.01V, analog disconnected protection is
invalid.
When F741 is set to 1, 2 or 3, the values of F400 and F406 should be set to 1V-2V, to avoid the
error protection by interference.
Analog disconnected protection voltage=analog channel input lower limit * F742. Take the AI1
channel for the example, if F400=1.00, F742=50, then disconnection protection will occur when
TC-Hydraulik - Rsdorfer Str. 8 - 25746 Heide - Lars Lornsen - T: +49 481 909 - 34 - l.lornsen@tc-hydraulik.de - www.tc-hydraulik.de

Table of Contents

Other manuals for Parker AC10 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC10 series and is the answer not in the manual?

Parker AC10 series Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
Analog Inputs2
Analog Outputs1
Communication OptionsModbus RTU
Protection RatingIP20
Input Voltage200-240VAC, 380-480VAC, 500-575VAC, 600VAC, 690VAC
Digital Outputs2
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Humidity5% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
BrakingBuilt-in dynamic braking