92 Pvd3665_Gb_Ex_August 2022
It is mandatory to connect 2 (green-yellow) ground cables between the motor
frame and machine.
the first one is connected to ground screw on the PCB inside the motor,
the other one is connected to the external motor housing
The connecting of these two grounding devices is mandatory in order to
comply with ATEX standard IEC/EN 60079-0.
The ground cable cross-section must be the same as the power cable cross-
section
3.8.3. Conversion Awg/kcmil/mm²:
Awg
kcmil
mm²
500
253
400
203
350
177
300
152
250
127
0000 (4/0)
212
107
000 (3/0)
168
85
00 (2/0)
133
67.4
0 (1/0)
106
53.5
1
83.7
42.4
2
66.4
33.6
3
52.6
26.7
4
41.7
21.2
5
33.1
16.8
6
26.3
13.3
7
20.8
10.5
8
16.5
8.37
9
13.1
6.63
10
10.4
5.26
11
8.23
4.17
12
6.53
3.31
14
4.10
2.08
16
2.58
1.31
18
1.62
0.82
20
1.03
0.52
22
0.63
0.32
24
0.39
0.20
26
0.26
0.13
3.8.4. Motor cable length
For motors windings which present low inductance values or low resistance values, the own
cable inductance, respectively own resistance, in case of large cable length can greatly
reduce the maximum speed of the motor. Please contact PARKER for further information.
Caution: It might be necessary to fit a filter at the servo-drive output if the
length of the cable exceeds 25 m. Consult us.
The length of the cable must be of 3 meters min.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker EX Series and is the answer not in the manual?

Parker EX Series Specifications

General IconGeneral
Fuel TypeGasoline
Control TypeElectronic
Valves per Cylinder4
Fuel SystemFuel Injected
Bore x Stroke86 mm x 86 mm

Related product manuals