35
BIFFI ICON 2000
InstructIon and operatIng manual
Motor
Start
position%
Stop
position%
On time On time On time
Off
time
Off
time
Off
time
Start position and stop position may be adjusted
from0%-100%separatelyinopeningand
closing direction.
ON time and OFF time may be adjusted from
1 sec - 200 sec separately in opening and
closing direction.
Configuration procedure
•MovethelocalselectortoOFFandthen
simultaneously press OPEN and STOP. Select
the language and then enter the password
according to the instructions (see “Entering
the set-up mode”). When the message
displayedis“SET-UPMODEOK?”press
YES. Press YES to select actuator set-up
menu, press NO to scroll the list of available
routines and then press YES to select
2-speed timer.
•PressYEStochangeclosedirection
parameters, press NO and then YES to
change only open direction parameters.
Closing direction
•PressYESifthestatusisOK,orNO
to change. Press YES to confirm
(status = On, enables 2-speed timer operation
in closing direction status = Off, disables
timer operation in closing direction).
•PressYESifthepositionvaluewherepulsing
control starts is correct, press NO to scroll
the list of available values. Press YES when
the value is correct.
•PressYESifthepositionvaluewherepulsing
control stops is correct, press NO to scroll
the list of available values. Press YES when
the value is correct.
•PressYESifthevalueoftheONtimeof
pulsing control is correct, press NO to scroll
the list of available values. Press YES when
the value is correct.
•PressYESifthevalueoftheOFFtimeof
pulsing control is correct, press NO to scroll
the list of available values. Press YES when
the value is correct.
Opening direction
•PressYESifthestatusisOK,orNOto
change. Press YES to confirm (status = On
enables 2-speed timer operation in opening
direction status = Off, disables timer
operation in opening direction).
•PressYESifthepositionvaluewherepulsing
control starts is correct, press NO to scroll
the list of available values. Press YES when
the value is correct.
9.1.11 2-Speed timer
The “2-speed timer” routine is used to extend
the actuator travelling time in opening and/or
closing direction, by driving the motor by
pulses which duration (ON and OFF time) is
configurable. Pulsing control can be applied to
full travel or only a part of it.
•PressYESifthepositionvaluewherepulsing
control stops is correct, press NO to scroll
the list of available values. Press YES when
the value is correct.
•PressYESifthevalueoftheONtimeof
pulsing control is correct, press NO to scroll
the list of available values. Press YES when
the value is correct.
•PressYESifthevalueoftheOFFtimeof
pulsing control is correct, press NO to scroll
the list of available values. Press YES when
the value is correct.
9.1.12 BUS (or FDI control)
This routine is only available if a fieldbus
interface card is present. The routine allows
setting the most important parameters
(node address, termination, etc.) necessary
to connect the actuator to a fieldbus. If the
ICON 2000 was set to work with fieldbus, but
the fieldbus card is not present, a Hardware
alarm will be generated. Different interfaces
are available to connect the ICON 2000 to
different types of fieldbus. If the bus interface
is LonWorks, the routine “BUS” changes in
“FDI control”. See the specific manuals for
instruction and setting of the above modules.
9.1.13 Miscellaneous
It includes different types of routines as “time
and date”, “factory settings”, “lithium battery”,
“torque profile”, etc. used only for special
application or in particular conditions.
9.1.13.1 Time and date
Time and date are used in maintenance
functions to associate the time information to
the memorized event (torque profile, alarm
log, maintenance request, etc.). Time and date
are entered at the time of manufacture, but
they can be adjusted during commissioning or
maintenance operations.
Configuration procedure
•MovethelocalselectortoOFFandthen
simultaneously press OPEN and STOP.
Select the language and enter the password
according to the instructions (see “Entering
the set-up mode”). When the message
displayedis“SET-UPMODEOK?”press
YES. Press YES to select actuator set-up
menu, press NO to scroll the list of available
routines and then press YES to select
Miscellaneous.
•PressYEStoenterthetimeanddateroutine.
•PressYESifthetimeiscorrect,pressNOto
change it.
•Enterhours,minutesandseconds.PressNO
to scroll the list of available values, press YES
to select.
•PressYESwhenthetimeiscorrect.
•PressYESifthedateiscorrect,pressNOto
change.
•Enterday,month,andyear.PressNOto
scroll the list of available values, press YES to
select.
•PressYESifthedateiscorrect.