9.1.13.2 Factory settings
The above routine resets the present configuration and restores the default configuration as
below:
Configuration procedure
•MovethelocalselectortoOFFandthen
simultaneously press OPEN and STOP. Select
the language and then enter the password
according to the instructions (see “Entering
the set-up mode”). When the message
displayedis“SET-UPMODEOK?”press
YES. Press YES to select the actuator set-up
menu, press NO to scroll the list of available
routines and then press YES to select
Miscellaneous.
•PressNotoscrollthelistofroutinesand
press YES to select factory configuration.
Press YES to download the standard
configuration, press NO to exit.
Stroke limits Close direction: CW
Close limit: by position
Open limit: by position
Torque set-up Closingtorque:40%
Openingtorque:40%
ESD set-up ESD action: close
ESD signal: present
ESD priority:
- ESD < motor thermostat
- ESD < torque limit
- ESD < local stop
- ESD > local controls
- ESD > 2-speed timer
- ESD < OFF
Remote controls Control type: 4 wires latched
Locals controls Control type: latched with instant reverse
LED’s color:
- green = open / opening
- red = close / closing
- yellow = alarm / warning
Output relay Default #1
2-speed timer Opening direction: off
Closing direction: off
Miscellaneous Lithium battery : absent
Torque profile: standard
Torqueby-pass:4%
Valve jammed: 4 sec.
9.1.13.3 Torque limits
Torque limits are used as a reference for
torque alarm and end of travel. With the option
“standard”, the torque limits are constant along
the full stroke. The limits can be configured
in the “stroke limits” or “torque set-up”
routines and determine the torque alarm or
end of travel situations. In the same particular
application it is useful to configure 3 different
torque thresholds for each travelling direction,
to limit separately the unseating, running
and ending torque. To select this option pick
“3-point limits” and then follow the torque
set-up and stroke limits routines (see figure).
ACTUATOR DIRECTION: OPENING
Openingtorque%ofnominal
Breakout limit
Ending limit
Position%
Running limit
ACTUATOR DIRECTION: CLOSING
Closingtorque%ofnominal
Breakout limit
Ending limit
Position%
Running limit
100%Clbrk%Clend%0%
0%Opbrk%Opend%100%
Configuration procedure
•MovethelocalselectortoOFFandthen
simultaneously press OPEN and STOP.
Select the language and enter the password
according to the instructions (see “Entering
the set-up mode”). When the message
displayedis“SET-UPMODEOK?”press
YES. Press YES to select actuator set-up
menu, press NO to scroll the list of available
routines and then press YES to select
Miscellaneous.
•PressNOandthenNOtoselect“torque
mode”. Press YES if setting is correct, press
NO to change. Press YES when the value is
correct.
•Repeatstrokelimitssettingroutine.