EasyManuals Logo

Pepperl+Fuchs AS-I 3.0 PROFIBUS User Manual

Pepperl+Fuchs AS-I 3.0 PROFIBUS
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #74 background imageLoading...
Page #74 background image
26.9.2013
74
AS-i 3.0 PROFIBUS Gateway in Stainless Steel
Appendix: Example for startup on a Siemens S7
Default: Setting of the ExtDiag flag on double address is disabled.
Freeze Diagnosis
The diagnostic data are continuously updated during runtime. If this is not de-
sired, this parameter can be used to disable continuous updating. Updating then
takes place only when this is required by the PROFIBUS standard.
AS-i Input Change Buffers
Default: Disabled.
Download Slave Parameters
Based on this entry the parameter bits can be downloaded for each AS-i slave.
These are then sent to the connected AS-i slave when the AS-i cycle is started.
Sending of the set parameters bits can be disabled with this value.
Default: Sending of the AS-i parameter bits enabled.
AS-i-Parameter Slave 1/1A...
The parameter bits send to this AS-i slave can be selected in the drop down win-
dow. The settings which are made with the parameters bits can be found in the
data sheet for the corresponding slave.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pepperl+Fuchs AS-I 3.0 PROFIBUS and is the answer not in the manual?

Pepperl+Fuchs AS-I 3.0 PROFIBUS Specifications

General IconGeneral
BrandPepperl+Fuchs
ModelAS-I 3.0 PROFIBUS
CategoryGateway
LanguageEnglish

Related product manuals