AS-i 3.0 PROFIBUS Gateway in Stainless Steel
Appendix: Example for startup on a Siemens S7
12.2.4.1 General DP parameters
Startup when nominal configuration is not the same as actual configuration:
Use this parameter to specify whether the AS-i circuit should be started up even if
the AS-i circuit has a different configuration than the stored AS-i configuration.
12.2.4.2 Device-specific parameters
Acyclic Communication
Turning acyclic PROFIBUS DP communication on/off according to the DPV1
standard.
Default: Communication turned on according to DPV1.
AS-i Flags
Specifies whether the AS-i flags are sent in the PROFIBUS diagnostic.
Default: Transmission in the PROFIBUS diagnostic data.
List of Configuration Errors
The VBG-PB-K30-D-S saves a list of all AS-i slaves which have triggered a
present configuration error. This list can be sent with the PROFIBUS diagnostic
data.
Default: Transmission in the PROFIBUS diagnostic data.