OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 24
2.4.1.8 IN-TANK LEAK TEST – HISTORY LOG
Log
Inventory Inventory
deLivery Deliveries
SALES Bulk Sales
tHEFtS Thefts
Orders Product Reordering Report
Water Bottom Water Removal
tank Leak In-Tank Leak Test – Detailed Results
Leak Hist In-Tank Leak Test – History
LIne Leak LS300 Line Leak Test
ALArMS Alarms
Events Events
return Return
Leak Hist In-Tank Leak Test History: A summarized version of the In-Tank Leak Test Results Log. The Leak
History Log may be modified at the completion of any given test. All data contained in this Log is copied
from the Tank Leak Log detailed on the previous page. For each Tank Channel, the Leak History Log
stores the latest passing test result for each of 14 months (the current month and 13 months prior). If
there is no passing test for a given month, the latest completed test is stored. See Tank Leak Log for
details regarding the Logging of Detailed In-Tank Leak Tests.
Record Storage Capacity: 168. 14 per Tank Channel.
TMS Configuration Prerequisites: N/A
Group ID: Record Number.
Record Identification Data:
tank id Tank ID Number: As Assigned in the Configuration menu, Tank submenu.
tank Name Tank Name: As Assigned in the Configuration menu, Tank submenu.
Prod type Product Type: As Assigned in the Configuration menu, Tank submenu.
mm.dd.yy Month.Day.Year: Date the scheduled Inventory Snapshot was recorded.
Note: an empty record will show 00.00.00.
Starttime Start Time: Time the In-Tank Leak Test began.
Note: time stored in 24 hr. format
Examples 12’00 = 12 Noon 23’59 = 11:59 PM 00’00 = Midnight
End time End Time: Time the In-Tank Leak Test completed.
Note: time stored in 24 hr. format
Examples 12’00 = 12 Noon 23’59 = 11:59 PM 00’00 = Midnight
Captured Data:
LeakLimit Leak Limit: Leak Threshold for determining Pass/Fail. See Configuration menu, Tank Leak
submenu, Leak Limit setting.
Rate GPH Leak Rate GPH/LPH: Observed average hourly gain/loss of Gross Volume.
ResULt Test Result: PASS or FAIL. In-Tank Leak Test result.
Exit Leak History submenu:
Return Return: Press EDIT (TEST) to exit Leak History submenu.
Note: Press STEP (MODE) to return to top of Leak History submenu showing mm-dd
(Month-Day)