2.4.3.8 SYSTEM CONFIGURATION – RELAY SITE
Config
Header Header – General System Settings
tank Tank – Tank Channel specific including geometry and SetPoints
Probe Probe – Level Gauging Probe settings
ReLy tank Relay Tank – Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC – Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor – Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP – Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site – Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode – Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft – Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test – Setup
AnaLogout Analog Outputs
ReLy Site Relay – Site-Specific Conditions: The TMS can report select conditions are specific to the Site and
not necessarily a specific probe or sensor. Each site-specific condition can affect up to three relay
outputs. The TMS3000 currently supports up to 32 Relay Outputs and the TMS2000 systems
currently support up to 18 Relay Outputs.
tHeft Theft Trigger: A loss of Product during hours that the facility should be closed is defined as a
Theft. This is configured in the Configuration menu in both the Tanks and Theft submenus. A
Theft can affect up to three relays.
Entry Type: numeric list
Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
Note: Each assignment separated by decimal point.
Default/Initialized value: no.no.no
PowerfaiL Power Fail Trigger: A past Power Failure of a duration of at least 1-2 minutes resulting in a
Warning 21 can affect up to three relays. The Warning 21 is also recorded in the Events Log.
Entry Type: numeric list
Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
Note: Each assignment separated by decimal point.
Default/Initialized value: no.no.no
SYS Error System Error Trigger: Any System Error including Probe, Sensor, and Memory Errors can affect
up to three relays. These Errors would also be recorded in the Events Log.
Entry Type: numeric list
Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
Note: Each assignment separated by decimal point.
Default/Initialized value: no.no.no
Return Return: Press EDIT (TEST) to exit Relay Site submenu.
Note: Press STEP (MODE) to return to top of Relay Site submenu showing tHeft (Theft)