OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 69
2.4.3.17 SYSTEM CONFIGURATION – ANALOG OUTPUT
Config
Header Header – General System Settings
tank Tank – Tank Channel specific including geometry and SetPoints
Probe Probe – Level Gauging Probe settings
ReLy tank Relay Tank – Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC – Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor – Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP – Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site – Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode – Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft – Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test – Setup
AnaLogout Analog Outputs
AnaLogout Analog Outputs: Enable individual Analog Output Channels, most commonly used as 4-20 mA
Outputs, to represent a specific Tank Channel and a volume, level, or temperature option. The
Group ID identifies the specific Analog Output Channel being configured.
AnaLog En Analog Output Enable: Enable the Analog Output Channel by selecting the Tank Channel to be
represented on the selected output.
Entry Type: numeric list
Range Limits: Tank Channel 1-12. Select NO to disable the output.
Default/Initialized value: tnk no
Data SeL Data Select: Choose the data from the selected Tank Channel being represented on the
specific Analog Output Channel.
Entry Type: select list
Range Limits: gr VoL: Gross Volume
nEtVoL: Net Volume
PrdLvL: Product Level
h2oLvL: Bottom Water Level
tEmP F: Temperature. Shows TEMP C for Metric firmware TMS systems.
Default/Initialized value: gr VoL
gain Gain: Adds support for 0-1 mA Output Mode by selecting a 0.05 (1/20) multiplier. DIP Switches
must be set for 0-20 mA Mode AND Gain set to 0.05 for this feature to work properly. All other
output modes must have the Gain set to the default of 1.00.
Entry Type: select list
Range Limits: 1.00, 0.05
Default/Initialized value: 1.00
Return Return: Press EDIT (TEST) to exit Analog Out submenu.
Note: Press STEP (MODE) to return to top of Analog Out submenu showing AnaLog En
(Analog Enable)