OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 57
2.4.3.11 SYSTEM CONFIGURATION SENSOR INPUT
Config
Header Header General System Settings
tank Tank Tank Channel specific including geometry and SetPoints
Probe Probe Level Gauging Probe settings
ReLy tank Relay Tank Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test Setup
AnaLogout Analog Outputs
Sensr inp Sensor (ISCC) Input: Configuration for each Sensor Input Channel to support the sensor model
connected including identification and TMS behavior. The Group ID shown corresponds to the
Sensor Input Number.
Sensr En Sensor Enable: Enables each Sensor Input Channel to use the sensor for Alarm purposes or
to exclusively use the Sensor to control of TMS functions like Relay Outputs.
Entry Type: Select list
Range Limits: Off: Disabled Sensor Input
Alarm: Used primarily for Alarm purposes resulting in an Alarm message being
displayed and an Alarm Log being generated. May also be used to control Relay
Outputs
Relay: Used exclusively to control Relay Outputs and will NOT generate an
Alarm on the TMS.
Default/Initialized value: OFF
type Sensor Type: The Model number of the Sensor connected to the Input.
Entry Type: select list
Range Limits: See Below Table
Default/Initialized value: ES820
ES820
ES820
ES8252
ES825-200F
HS100
HS100
LS600
LS600
LS610
LS610
rSU800
RSU800
rSU801
RSU801 (Future Use)
rSU802
RSU802 (Future Use)
OthEr
Other (3
rd
party float switch)
ES8251
ES825-100F
CritHi
Critical High
CritLo
Critical Low
Mode Sensor Mode: Specifies purpose of sensor as a Leak Sensor which lights up the Leak LED or
Other non-leak Sensor. This difference is also identified in the real-time interfaces as well as
the TMS Alarm Log.
Entry Type: select list
Range Limits: Leak, Other
Default/Initialized value: LEAk